Heating BTU calculator

Add up heat loss from the exposed surfaces of a room.

Measurements

Enter 12′ 6″, 12.5 ft or 3.8 m in a length field.

ft² if no unit
Estimated heat loss
3,769.752 BTU/h
Surface heat loss
2,629.752 BTU/h

A simple steady-state estimate. Equipment sizing needs a full load calculation.

How this is calculated

Verify before use. Have an HVAC professional confirm loads with Manual J and check equipment separately. This calculation represents the described surfaces and leakage only.

Multiply exposed surface area by the U-factor and indoor versus outdoor temperature difference. Add the specified air leakage load.

Worked example

Envelope surface area: 876 sq ft · Average U-factor: 0.079 BTU/(h·ft²·°F) · Indoor–outdoor design difference: 38 °F · Extra air leakage load: 1140 BTU/h

  1. Multiply exposed surface area by the U-factor and indoor versus outdoor temperature difference. Add the specified air leakage load.
  2. Using those inputs, the primary result is 3,769.752.

Sources

Frequently asked questions

What goes into envelope surface area?

Enter the measured or quoted envelope surface area for this job. Follow the unit shown on the field.

How is heating btu calculator calculated?

Multiply exposed surface area by the U-factor and indoor versus outdoor temperature difference. Add the specified air leakage load.

What changes if average u-factor (btu/(h·ft²·°f)) changes?

Enter the new average u-factor (btu/(h·ft²·°f)) and recalculate. Use the full precision shown in the result before transferring it to a dependent estimate.

What should I check before using the result?

A simple steady-state estimate. Equipment sizing needs a full load calculation.

How do I keep this calculation?

Use Copy result to capture the answer and its units.